![GE Multilin F650 Instruction Manual Download Page 885](http://html.mh-extra.com/html/ge-multilin/f650/f650_instruction-manual_572016885.webp)
APPENDIX B: MODBUS PROTOCOL
B.5 MEMORY MAP
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
B-113
0x2DCD
Analog Input Point 19
F004
1000 R/W
1 [0 , 32767]
0x2DCE
Analog Input Point 20
F004
1000 R/W
1 [0 , 32767]
0x2DCF
Analog Input Point 21
F004
1000 R/W
1 [0 , 32767]
0x2DD0
Analog Input Point 22
F004
1000 R/W
1 [0 , 32767]
0x2DD1
Analog Input Point 23
F004
1000 R/W
1 [0 , 32767]
0x2DD2
Analog Input Point 24
F004
1000 R/W
1 [0 , 32767]
0x2DD3
Analog Input Point 25
F004
1000 R/W
1 [0 , 32767]
0x2DD4
Analog Input Point 26
F004
1000 R/W
1 [0 , 32767]
0x2DD5
Analog Input Point 27
F004
1000 R/W
1 [0 , 32767]
0x2DD6
Analog Input Point 28
F004
1000 R/W
1 [0 , 32767]
0x2DD7
Analog Input Point 29
F004
1000 R/W
1 [0 , 32767]
0x2DD8
Analog Input Point 30
F004
1000 R/W
1 [0 , 32767]
0x2DD9
Analog Input Point 31
F004
1000 R/W
1 [0 , 32767]
0x2DE0
Confirmation address
W
1
Miscelaneous Settings
0x2DE2
Relay Out Of Service
F012
1000 R/W
1 0=DISABLED
1=ENABLED
0x2DE3
Local/Remote Blocked
F012
1000 R/W
1 0=OFF
1=ON
0x2DE4
Active Language
F004
1000 R/W
1 [0 , 1]
0x2DF5
Confirmation address
W
1
Ajustes Unidad Sobreintensidad Instantánea de Tierra Aislada Grupo 1 - Isolated Ground IOC 1 Settings
0x2DF6
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2DF7
Vh Level
F003
1
R/W
2
[2 , 70] V
0x2DF9
Il LEVEL
F003
1
R/W
2
[0.005 , 0.400] A
0x2DFB
Vl LEVEL
F003
1
R/W
2
[2 , 70] V
0x2DFD
Ih LEVEL
F003
1
R/W
2
[0.005 , 0.400] A
0x2DFF
Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x2E01
Time to inst
F003
1
R/W
2
[0.00 , 900.00] s
0x2E03
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E16
Confirmation address
W
1
Ajustes Unidad Sobreintensidad Instantánea de Tierra Aislada Grupo 2 - Isolated Ground IOC 2 Settings
0x2E17
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E18
Vh Level
F003
1
R/W
2
[2 , 70] V
0x2E1A
Il LEVEL
F003
1
R/W
2
[0.005 , 0.400] A
0x2E1C
Vl LEVEL
F003
1
R/W
2
[2 , 70] V
0x2E1E
Ih LEVEL
F003
1
R/W
2
[0.005 , 0.400] A
0x2E20
Delay
F003
1
R/W
2
[0.00 , 900.00] s
0x2E22
Time to inst
F003
1
R/W
2
[0.00 , 900.00] s
0x2E24
Snapshot Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E37
Confirmation address
W
1
Ajustes Unidad Sobreintensidad Instantánea de Tierra Aislada Grupo 3 - Isolated Ground IOC 3 Settings
0x2E38
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E39
Vh Level
F003
1
R/W
2
[2 , 70] V
0x2E3B
Il LEVEL
F003
1
R/W
2
[0.005 , 0.400] A
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...