CHAPTER 7: IEC 61850 PROTOCOL
7.2 IEC 61850 PROFILE FOR F650
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
7-207
Ct9
1, 2
Which additional cause diagnosis are supported
Y Unknown
Y Not-supported
Y Blocked-by-switching-hierarchy
N Select-failed
Y Invalid-position
Y Position-reached
N Step-limit
N Blocked-by-Mode
N Blocked-by-process
N Blocked-by-interlocking
N Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
N 1-of-n-control
N Abortion-by-cancel
Y Time-limit-over
N Abortion-by-trip
Y Object-not-selected
Edition 1 specific values:
N Parameter-change-in-execution
Edition 2 specific values:
Y Object-already-selected
N No-access-authority
N Ended-with-overshoot
N Abortion-due-to-deviation
N Abortion-by-communication-loss
N Blocked-by-command
N None
Y Inconsistent-parameters
Y Locked-by-other-client
N Parameter-change-in-execution
Ct10
1, 2
How to force a “test-not-ok” respond with SelectWithValue request
Device in local mode
Ct11
1, 2
How to force a “test-not-ok” respond with Select request
Ct12
1, 2
How to force a “test-not-ok” respond with Operate request
DOns:
Sending T=1
SBOns: Sending T=1
DOes:
Sending T=1
SBOes: Sending T=1
Ct13
1, 2
Which origin categories are supported / accepted
N bay-control
Y station-control
Y remote-control
N automatic-bay
Y automatic-station
Y automatic-remote
N maintenance
N process
Ct14
1, 2
What happens if the orCat value is not supported or invalid
DOns: control is rejected (Oper-
ObjectAccessDenied).
SBOns: control is rejected (Oper-
ObjectAccessDenied).
DOes: control is rejected (Oper-
ServiceError, ObjectAccessDenied).
SBOes: control is rejected (SBOw-
ServiceError, ObjectAccessDenied).
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...