CHAPTER 2: PRODUCT DESCRIPTION
2.5 TECHNICAL SPECIFICATIONS
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
2-15
FORWARD POWER (32FP)
Current, Voltage: ...................................................................... fundamental phasor (primary values)
Number of Stages:................................................................... 2
Pickup Level:............................................................................... 0.00 to 10000.00 MW in steps of 0.01 MW
Dropout Level: ........................................................................... 97% to 98% of the pickup level
Level Accuracy for Primary Magnitudes:..................... ±3% of complete range
Trip Delay (Two Stages):........................................................ 0.00 to 900.00 s in steps of 0.01 s
Timing Accuracy:..................................................................... ±3.5% of operate time or 50 ms (whichever is greater)
Block Time After Close: ......................................................... 0.00 to 900.00 s in steps of 0.01 s
Snapshot Events: ..................................................................... selectable by setting
DIRECTIONAL POWER (32)
Current, Voltage: ...................................................................... fundamental phasor (primary values)
Number of Stages:................................................................... 2
Pickup Level:............................................................................... -10000.00 to 10000.00 MW (primary values) in steps of 0.01 MW
Characteristic Angle (Two Stages): .................................. 0.00º to 359.99º in steps of 0.01º
Accuracy for Primary Magnitudes: ................................. ±3% of complete range
Trip Delay (Two Stages):........................................................ 0.00 to 900.00 s in steps of 0.01 s
Timing Accuracy:..................................................................... ±3.5% of operate time or 50 ms (whichever is greater)
Block Time After Close: ......................................................... 0.00 to 900.00 s in steps of 0.01 s
Snapshot Events: ..................................................................... selectable by setting
Operate Time:............................................................................ < 45 ms at 50 Hz, typically
WATTMETRIC ZERO-SEQUENCE DIRECTIONAL (32N)
Measured Power:..................................................................... zero sequence
Number of Elements: ............................................................. 6 (3 high level, 3 low level)
Voltage Pickup Level V
N
:....................................................... 2.00 to 70.00 V in steps of 0.01 V
voltage calculated from phases if auxiliary voltage is set to V
x
voltage measured from the 4th voltage transformer if auxiliary voltage is set to V
N
Level Accuracy for Voltage: ................................................ ±1% of reading from 10 to 208
Current Selection: .................................................................... I
N
(calculated from phases)
I
G
(measured from the 4th current transformer)
OC Pickup Level: ....................................................................... 0.005 to 0.400 A in steps of 0.001
Level Accuracy for Current: ................................................ ±0.5% of the reading ± 10 mA from 0.05 to 10.00 A
±1.5% of the reading for higher values
OC Pickup Delay:...................................................................... 0.00 to 600.00 s in steps of 0.01 s
Power Pickup Level: ................................................................ 0.01 to 4.50 W in steps of 0.01 W
Characteristic Angle (MTA):.................................................. 0º to 360º in steps of 1º
Power Pickup Delay:............................................................... 0.00 to 600.00 s in steps of 0.01 s
Level Accuracy for Power:................................................... ±2.5% of the reading at -0.8
≤
PF
≤
-1 and 0.8 < PF
≤
1
Curve Shapes: ........................................................................... Inverse Curve
Definite Time
FlexCurve
TM
A/B/C/D user curves
Curve Multiplier (Time Dial): ................................................ 0.02 to 2.00 s in steps of 0.01 s
Tripping Time Accuracy: ...................................................... ±3.5% of operate time or 50 ms whichever is greater
Snapshot Events: ..................................................................... selectable by setting
Operate Time:............................................................................ < 45 ms at 50 Hz, typically
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...