![GE Multilin F650 Instruction Manual Download Page 61](http://html.mh-extra.com/html/ge-multilin/f650/f650_instruction-manual_572016061.webp)
CHAPTER 2: PRODUCT DESCRIPTION
2.5 TECHNICAL SPECIFICATIONS
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
2-25
2.5.10 Communications
FRONT PORT:
Front port:
COM2
Type:
RS232/USB
Baud Rate:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200 baud
Default Baud Rate:
19200 baud
Protocols:
ModBus
®
RTU/DNP 3.0
Typical Distance:
3 m
Isolation:
2 kV
ASYNCHRONOUS REAR PORTS:
None or two rear ports (depending on model):
COM1, COM2 (rear COM2 multiplexed with front port)
Type (depending on model):
Model F
None
Model A
Redundant RS485
Model X
Redundant RS485 + fiber CAN for inputs/outputs module
Model P
Redundant 1mm-plastic F.O.
Model Y
Redundant 1mm-plastic F.O. + fiber CAN for inputs/outputs module
Model G
Redundant multimode glass F.O.
Model Z
Redundant multimode glass F.O. + fiber CAN for inputs/outputs module
Model C
Cable CAN port for I/O module
Model M
Cable CAN port for I/O module (cable) + RS485 (ModBus RTU)
Optic Features for ST Connector Devices:
Wave length: 1300nm
Fiber type: multimode 62.5/125
μ
m or 50/125
μ
m
Baud Rate:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200 baud
Default Baud Rate:
19200 baud
Protocols:
ModBus
®
RTU/DNP 3.0/IEC103
Typical Distance:
1200 m for cooper cable, 1000 m for glass fiber and 50 m for plastic fiber
Isolation:
2 kV
CAN PORT:
Rear Port:
CAN port in models C, M, X, Y, Z for asynchronous rear ports
Type:
Multimode glass F.O. port with ST connectors
Fiber Wavelength:
820 nm
Fiber Type:
multimode 62.5/125
μ
m or 50/125
μ
m
Maximum Recommended Length:
300 m for cooper cable and glass fiber
Isolation:
2 kV
ETHERNET PORT:
Rear port:
For models B, C, D, E:
ETH_1/ ETH_2
For models G, H, J, K, L, M:
ETH_E/ ETH_A/ ETH_B
Type (depending on model):
Model B:
10/100BaseTX self-negotiable
Model C:
10/100 100Base FX
Model D:
10/100 redundant 100BaseFX (Physical media redundancy)
Model E:
Redundant 10/100BaseTX self-negotiable ports
Model G:
1588, 10/100 Base TX* + 100 Base TX
Model H:
1588, 10/100 Base TX* + 100 Base FX
Model J:
PRP, 1588, 10/100 Base TX* + Redundant 100 Base FX
Model K:
PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base FX
Model L:
PRP, 1588, 10/100 Base TX* + Redundant 100 Base TX
Model M:
PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base TX
(*) Note: This Ethernet port (ETH_E) is intended only for maintenance purposes.
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...