APPENDIX G: REDUNDANCY PROTOCOL
G.1 PRP AND HSR ETHERNET PROTOCOLS
GEK-106310-AF
F650 DIGITAL BAY CONTROLLER
g-3
Figure G-2: Example of HSR with HSR ring
Definitions:
•
PRP – Parallel Redundancy Protocol - redundancy protocol for high availability in substation automation networks
based on IEC 62439-3 Clause 4 and applicable to networks based on Ethernet technology (ISO/IEC 8802-3).
•
OSI - Open Systems Interconnection - model defined by the International Organization for Standardization (ISO) for
standardizing the functions of a communication system in terms of abstraction layers. Similar communication
functions are grouped into logical layers. A layer serves the layer above it and is served by the layer below it. There
are 7 layers: physical, data link, network, transport, session, presentation, application.
•
DANP – Doubly Attached Node running PRP – a node that has two ports which operate in parallel and are attached to
the upper layers of the OSI communications stack through a Link Redundancy Entity module.
•
DANH – Doubly Attached Node with HSR protocol.
•
LRE - Link Redundancy Entity – module operating at the link layer of the OSI stack and responsible for handling
duplicates and managing redundancy.
•
SAN – Singly Attached Node – regular nodes with non-redundant network adapters
•
RedBox – device attaching singly attached nodes (SANs) to a redundant network.
•
RCT – Redundancy Check Trailer – PRP trailer added to frames and consisting of the following fields:
~16-bit sequence number (SeqNr);
~4-bit LAN identifier (LanId);
~12 bit frame size (LSDUsize)
~16-bit suffix (PRPsuffix).
Summary of Contents for F650
Page 406: ...6 58 F650 DIGITAL BAY CONTROLLER GEK 106310 AF 6 5 RECORDS CHAPTER 6 ACTUAL VALUES ...
Page 994: ...H 2 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 995: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 3 ...
Page 996: ...H 4 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 998: ...H 6 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 999: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 7 ...
Page 1002: ...H 10 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...
Page 1003: ...APPENDIX H FACTORY DEFAULT LOGIC GEK 106310 AF F650 DIGITAL BAY CONTROLLER h 11 ...
Page 1004: ...H 12 F650 DIGITAL BAY CONTROLLER GEK 106310 AF APPENDIX H FACTORY DEFAULT LOGIC ...