SETTINGS LIST
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
0
0
Pipe length
setting
0
0 Standard (40~65m)
l
¡
-
*1
Pipe length means the length
between master outdoor unit
and the farthest indoor unit.
0
1 Short (less than 40m)
0
2
Medium (65~90m)
0
3
Long 1 (90~120m)
0
4
Long 2 (120~150m)
1
0 Sequential start
shift
0
0
Normal
l
¡
-
*1
The start-up timing of outdoor
unit (compressor) can be set
up so that it can delay several
seconds.
This feature is useful when
multiple number of outdoor units
are installed and turned on at
the same time
to limit the starting current.
0
1
21sec. Delay
0
2 42sec. Delay
0
3 63sec. Delay
1
1 Cooling
capacity shift
0
0
Normal mode
l
¡
-
*1
0
1 Save energy mode 1
0
2 High power mode 1
0
3
High power mode 2
0
4 Forbidden
1
2 Heating
capacity shift
0
0
Normal mode
l
¡
-
*1
0
1 Save energy mode
0
2 High power mode 1
0
3
High power mode 2
1
3 Forbidden
0
0 Forbidden
l
Setting forbidden
0
1 Forbidden
2
0
Switching
between
forced stop or
emergency stop
0
0 Forced stop
l
¡
-
*1
This mode selects the pattern of
the stop function to be operated
by the external input terminal
(CN134).
•Forced stop: The air conditioner
stays stopped even if input from
the CN134 is stopped.
•Emergency stop: The air
conditioner returns to the
original operation if input
from the CN134 is stopped.
Furthermore, the air conditioner
does not accept the operation of
the indoor unit when emergency
stop is actuated.
0
1 Emergency stop
*1: Do not set this for outdoor units with Slave setting.
- (06 - 105) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...