FUNCTION SETTING
Pressing the SET BACK button, select a remote controller address (select the indoor
4)
unit you want to operate).
Pressing the SET TIME < button or the SET TIME > button, to select the function
5)
number.
Pressing the SET TEMP. V button or the SET TEMP.
6)
Λ
button, to select the setting
number. The display flashes during setting number selection.
Pressing the TIMER SET button, confirm the setting.
7)
(The data will be transferred to the indoor unit.)
Function number
Ex.) When remote controller address “01” is
selected
Remote controller address
Ex.) Function number : 30, Setting number : 01
Setting number
NO GOOD
When the data was not set up on the indoor
●
unit (-- is displayed.)
Set up the data again according to the
●
procedure in step 5), 6) above.
GOOD
When the data was normally set up on the indoor
unit
(Flashing display changes to illuminated display.)
- (06 - 122) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...