Example 4 (One indoor unit connection)
z
<Connection of ARXC90LATH and AJ
A90LALH>
Model
Capacity
(kW)
Total
capacity
(kW)
Connectable indoor
unit capacity
Judgement
Min.
Max.
Outdoor unit
AJ
A90L
28.0
28.0
50%
14.0
150%
42.0
≤
≤
14.0 < 25.0 < 42.0 → OK
Indoor unit 1 ARXC90
25.0
25.0
<Connection of ARXC72LATH and AJ
A72LALH>
Model
Capacity
(kW)
Total
capacity
(kW)
Connectable indoor
unit capacity
Judgement
Min.
Max.
Outdoor unit
AJ
A72L
22.4
22.4
50%
11.2
150%
33.6
≤
≤
11.2 < 22.4 < 33.6 → OK
Indoor unit 1
ARXC72
22.4
22.4
<Connection of ARXC60LATH and AJ
A72LALH>
Model
Capacity
(kW)
Total
capacity
(kW)
Connectable indoor
unit capacity
Remarks
Min.
Max.
Outdoor unit
AJ
A72L
22.4
22.4
50%
11.2
150%
33.6
No good
Indoor unit capacity below 20kW is
not allowed
(For one indoor unit connection)
Indoor unit 1 ARXC60
18.0
18.0
Capacity ratio
80%
Outdoor unit
Indoor unit 1
Capacity ratio
89%
Outdoor unit
Indoor unit 1
Capacity ratio
600%
Outdoor unit
Indoor unit 1
- (06 - 05) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...