662636 PIPE SIZE
PIPE DIAMETER, RECOMMENDED MATERIAL AND WALL THICKNESS
Nominal Diameter
(in)
1/4"
3/8"
1/2"
5/8"
3/4"
7/8"
1-1/8"
1-3/8"
1-5/8"
Outside Diameter
(mm)
6.35
9.52
12.70
15.88
19.05
22.22
28.58
34.92
41.27
Material
JIS H3300 C1220T-O or equivalent *1
JIS H3300 C1220T-H or equivalent *2
Wall Thickness *3
(mm)
0.8
0.8
0.8
1.0
1.2
1.0
1.0
1.2
1.43
*1: Allowable tensile stress ≥ 33 (N/mm
2
)
*2: Allowable tensile stress ≥ 61 (N/mm
2
)
*3:
Endurance pressure of the pipe must be 4.2 MPa
.
Please select the pipe size in accordance with local rules.
PIPE SIZE SELECTION
Caution
●
After referring to "COOLING CAPACITY TABLE" followed, select each Pipe size, Separation
tube and Header from "COOLING CAPACITY TABLE" of Outdoor unit and Indoor unit
connected in the system.
Pipe size table "A"
z
(Between outdoor unit to outdoor unit branch kit)
HP
Model
code
Outdoor
unit cooling
capacity (kW)
Outside diameter mm (in)
Branch kit
Liquid pipe
Gas pipe
8
72
22.4
12.70 (1/2")
22.22 (7/8")
UTR-CP567
X
10
90
28.0
12.70 (1/2")
22.22 (7/8")
12
108
33.5
12.70 (1/2")
28.58 (1-1/8")
14
126
40.0
12.70 (1/2")
28.58 (1-1/8")
16
144
45.0
12.70 (1/2")
28.58 (1-1/8")
Outdoor
unit1
(Master)
Outdoor unit branch kit (optional)
First separation tube (optional)
separation tube (optional)
Pipe size
(table"A")
Pipe size
(table"B")
Pipe size
(table"C")
Pipe size
(table"D")
Outdoor
unit2
(Slave1)
Outdoor
unit3
(Slave2)
- (06 - 20) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...