PROCEDURE IN BRIEF FOR MAKING XIF & REGISTER DATA TO
NETWORK CONVERTOR (UTY5VLGX)
Note: For detail information, please check the Application Manual
STEP 1: Connect the PC and Network Convertor (UTY-VLGX) .
Connection will be done by the connector cable provided as an accessory item of
UTY-VLGX.
STEP 2: Install Tool for Network Convertor (software) for UTY-VLGX in PC.
Tool for Network Convertor is the accessory item of UTY-VLGX.
STEP 3: Set Network Convertor (UTY-VLGX) to Installation Mode.
STEP 4: Initial setting of Indoor Unit & Outdoor Unit Addresses by using the Tool for Network
Convertor.
STEP 5: Resister the initial setting data to UTY-VLGX. Click ‘Register’ dialog.
STEP 6: Set Configuration Properties.
It is the communication properties of UTY-VLGX. Select the following Communication
items & Communication type if necessary. Otherwise, communication will be taken
place by the Default values.
Select Communication items
●
-Event Driven communication or Cyclic communication.
(Default: Cyclic 3minutes)
-Communication Interval Time during turning ON all together.
(Default: 3 minutes)
Select Communication type (to communicate data with BMS)
●
- Communicate only when changing network variable or communicate all network
variable. (Default: Only when changing network variable)
- Communicate only when changing room temperature value.
(Default: Room temperature changed value 1°C)
STEP 7: Apply the Configuration Properties data to UTY-VLGX. Click ‘Apply’ dialog.
STEP 8: Making / Modifying XIF, and transfer XIF data by USB memory or floppy disk for
binding.
STEP 9: Reset Network Convertor (UTY-VLGX) to press ‘Reset SW7’.
STEP 10: Turn OFF the power. After that, remove the connection of PC & Network Convertor
(UTR-VLGX) respectively.
In this stage, Network Convertor (UTY-VLGX) is ready for binding & commissioning.
Important
: Network Convertor will not operate if,
VRF network system address (Outdoor & Indoor units address) allocation information
●
are not registered to Network Convertor.
XIF data information and VRF network system address allocation information must
●
not be same.
Binding & Commissioning is not executed.
●
- (05 - 70) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...