662656 ADDITIONAL CHARGE CALCULATION
The outdoor unit is charged refrigerant at the factory.
●
Additional refrigerant required to be charged on site depending on pipe length and outdoor
●
unit model.
The additional refrigerant charge amount is calculated according to the following formula.
●
The overall refrigerant amount should not be exceed 30kg per outdoor unit.
●
Round up the calculated result to two decimal places.
●
CALCULATION OF ADDITIONAL CHARGE REFRIGERANT
66 Calculation of additional amount for outdoor unit
26 Calculation of additional amount for pipe length
36 Calculation of additional charge refrigerant
C = A + B =
Round up C to 2 decimal place.
46 Calculation of factory charged amount
56 Total refrigerant amount check
E = C + D =
Note : Check the total refrigerant amount under the following conditions6
Condition
Computational formula
For 1 outdoor unit per refrigerant system : Total amount of refrigerant ≤ 31.5kg
E ≤ 31.5kg
For 2 outdoor units per refrigerant system : Total amount of refrigerant ≤ 63.0kg
E ≤ 63.0kg
For 3 outdoor units per refrigerant system : Total amount of refrigerant ≤ 94.5kg
E ≤ 94.5kg
When total refrigerant amount exceed limitation.
Reduce pipe length for refrigerant system.
●
Change the refrigerant system configuration.
●
kg
kg
Model
HP
d
Factory charged
amount (kg)
a
Additional amount
for outdoor unit (kg)
AJ
A72LALH
8
11.20
0
AJ
A90LALH
10
11.20
0
AJ
108LALH 12
11.80
1.20
AJ
126LALH
14
11.80
3.30
AJ
144LALH
16
11.80
3.30
Diameter of liquid
pipe (mm)
b
Additional amount for
pipe length (kg/m)
ø6.35
0.021
ø9.52
0.058
ø12.70
0.114
ø15.88
0.178
ø19.05
0.268
a : Outdoor unit 1
additional amount for
outdoor unit
kg
a : Outdoor unit 2
additional amount for
outdoor unit
kg
a : Outdoor unit 3
additional amount for
outdoor unit
kg
A=
=
+
+
To
tal
kg
Total
length of
ø15.88mm
liquid pipe
b :
x 0.178
kg/m
m
kg
Total
length of
ø19.05mm
liquid pipe
b :
x 0.268
kg/m
m
kg
Total
length of
ø12.70mm
liquid pipe
b :
x 0.114
kg/m
m
kg
Total
length of
ø9.52mm
liquid pipe
b :
x 0.058
kg/m
m
kg
Total
length of
ø6.35mm
liquid pipe
b :
x 0.021
kg/m
m
kg
+
+
+
+
B=
=
To
tal
kg
d : Outdoor unit 1
factory charged amount
kg
d : Outdoor unit 2
factory charged amount
kg
d : Outdoor unit 3
factory charged amount
kg
D=
+
+
=
To
tal
kg
- (06 - 26) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...