CAUTION
Keep the "piping limitation" for correct operation6
Allowable height difference:
z
If the height difference between the indoor unit and outdoor unit is larger than the allowable value:
The pressure loss will be larger → Insufficient cooling and heating
*
The refrigerant in liquid pipe will flush → Refrigerant flow noise generate at indoor unit
*
The refrigerant oil will not return → Insufficient refrigerant oil resulting in compressor damage
*
If the height difference between indoor unit is larger than the allowable value:
The refrigerant flow balance will be poor → Insufficient cooling and heating (poor balance)
*
Refrigerant oil will collect in the piping or non-operating indoor units
*
→ Insufficient refrigerant oil resulting in compressor damage
Pipe length:
z
If the pipe length is longer than prescribed:
The pressure loss will be larger → Insufficient cooling and heating
*
Too much refrigerant will be charged → Liquid backs up resulting in compressor damage
*
The refrigerant oil will not return → Insufficient refrigerant oil resulting in compressor damage
*
Pipe size:
z
If the pipe size is larger than designated size:
The refrigerant flow velocity will drop. Refrigerant oil will not return to the outdoor unit.
*
→ Insufficient refrigerant oil resulting in compressor damage
The refrigerant in liquid pipe will flush easily → Insufficient cooling and heating
*
If the pipe size is smaller than designated size:
The refrigerant circulation volume will drop → Insufficient cooling and heating
*
The pressure loss will be larger → Insufficient cooling and heating
*
Indoor unit connected capacity:
z
If the indoor unit connected capacity is larger than the system capable capacity:
Insufficient system performance → Insufficient cooling and heating
*
When heating, refrigerant will collect in non-operating indoor units resulting in an insufficient
*
refrigerant circulation volume → Insufficient cooling and heating
The refrigerant oil will not return → Compressor damage
*
If the indoor unit connected capacity is too small compared to the system capacity:
The liquid return will be too great → Compressor damage
*
The refrigerant will concentrate in the operating unit
*
→ Continuous operation will become difficult due to triggering of the protection in
response to the pressure high-rise, etc., and noise will be generated by the refrigerant flow
when heating
- (06 - 19) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...