Main pipe connection
z
Make sure to arrange the pipe horizontally or upward as shown in the following to prevent oil
from accumulating into stopped outdoor unit.
If the pipe length between outdoor unit branch kit and outdoor unit branch kit (or slave unit) is
*
longer than 2 m, or a lower pipe line exists between outdoor units, traps for gas pipe should
be arranged to eliminate oil from entering into and remaining at pipes and the stopped outdoor
unit. (See example below)
a) Installable patterns
To indoor unit
To indoor unit
Outdoor
unit1
Outdoor
unit1
Outdoor
unit1
Outdoor
unit1
Outdoor
unit1
Outdoor
unit1
Outdoor
unit2
Outdoor
unit2
Outdoor
unit2
Outdoor
unit2
Outdoor
unit2
Outdoor
unit2
Outdoor
unit3
Outdoor
unit3
Outdoor
unit3
Outdoor
unit3
Outdoor
unit3
Outdoor
unit3
To indoor unit
To indoor unit
To indoor unit
To indoor unit
b) Non-installable patterns
Good
Good
Good
No Good
No Good
No Good
Example
To indoor
unit
To indoor
unit
Trap
Trap
Trap height : 200mm or more
2m or less
2m or more
Gas pipe
Gas pipe
Lower pipe
Outdoor
unit1
Outdoor
unit1
Outdoor
unit2
Outdoor
unit2
Outdoor
unit3
Outdoor
unit3
- (06 - 35) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...