CONTROLLER AND CONVERTOR
Model
Maximum
connectable
units in one VRF
network system
Remarks
C
on
tro
ller
C
en
tra
l C
on
tro
l
System
Controller
UTY-APGX
1
Max.controllable VRF network system : 4
Max.controllable remote controller
groups : 1600 per 4 VRF network system
Max.controllable indoor unit : 1600 per 4
VRF network system
Max.controllable groups : 1600 per 4
VRF network system
Touch Panel
Controller
UTY-DTG
16
*1:Note
Max.controllable remote controller
groups : 400
Max.controllable indoor unit : 400
Max.controllable groups : 400
Group Remote
Controller
UTY-CGG
(64)
When Group Remote Controller is used,
Network Convertor (UTY-VGGX) is
required.
Max controllable remote controller
groups : 8
Max controllable indoor units : 96
In
di
vi
du
al C
on
tro
l
Wired Remote
Controller
UTY-RNK
Max controllable indoor units : 16
Simple Remote
Controller (with
master control)
UTY-RSK
Max controllable indoor units : 16
Simple Remote
Controller
(without master
control)
UTY-RHK
Max controllable indoor units : 16
Wireless
Remote
Controller
UTY-LNH
A
da
pt
or / C
on
ve
rto
r
Signal
Amplifier
UTY-VSGX
8
The signal amplifier is required when
500m or more in transmission line length
or connected unit exceeds 64units.
Network
Convertor
UTY-VGGX
Used for
connecting split
system : 100
Total number
of refrigerant
system and
Network
convertor is
maximum 100.
Max connectable Single split or Big multi
type in a UTY-VGGX : 16 units.
Used for
connecting
Group Remote
Controller : 16
*1:Note
Max connectable Group Remote
Controller : 4 units.
One Network Convertor (UTY-VGGX)
covers 2 refrigerant systems.
Network
Convertor for
L
ON
W
ORKS
®
UTY-VLGX
1
Max controllable indoor units : 128
External
Switch
Controller
UTY-TEKX
Max connectable indoor units : 16
*1 Note : For one VRF network system, total number of Touch Panel Controller, Network Convertor
for Group Remote Controller is 16, including one Network Convertor for L
ON
W
ORKS
®
.
- (06 - 07) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...