CASSETTE TYPE
Drain
●
lift-up
pipe restrictions:
(1) Lift-up height ≤ 850mm (from ceiling)
(2) Drain hose (pipe) length ≤ 300mm (between indoor unit and lift-up pipe)
When a dimensions exceed the above restrictions will cause water leakage.
●
300mm or less
M
ax
. 8
50
m
m
Attached band
Downward
gradient 1/100
or more
Horizontal or
upward gradient
VP25 (Local
arrangement)
VP25
1.5m to 2.0m
Hanging fitting
Downward gradient 1/100 or more
Air bleeding
Rise
Trap
No good
drain hose
(accessory)
- (06 - 164) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN