Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
4424444 WALL MOUNTED TYPE
Model name
AS
A18LATH
AS
A24LATH
AS
A30LATH
Power source
230V ~, 50Hz
Available voltage range
198 to 264 V
Capacity
Cooling
kW
5.6
7.1
8.0
Heating
6.3
8.0
8.8
Input power
W
63
74
73
Fan
Airflow
rate
High
m
3
/ h
870
940
980
Med
700
720
870
Low
540
600
750
Type x Quantity
Cross flow × 1
Motor output
W
38
38
38
Sound pressure
level
High
dB(A)
43
45
45
Med
37
39
42
Low
30
33
39
Heat exchanger
Length
mm
855
855
Fin pitch
1.20
1.20
1.40
Rows x Stages
2 × 16
Face Area
m
2
0.29
Pipe type (Material)
Grooved H-pin (Copper)
Fin
Type (Material)
Slit (Aluminium)
Surface
treatment
Hydrophilic coating
Air filter
Type
Deodorization / Anti-mold
Net material
PP monofilament net
Enclosure
Material
Plastic
Colour
White (N9)
Dimensions
(H x W x D)
Net
mm
320 × 1,120 × 220
Gross
348 × 1,240 × 427
Weight
Net
kg
16
Gross
22
Connection
pipe diameter
Liquid (Flare)
mm
ø 9.52
Gas (Flare)
ø 15.88
Drain
ø 12(I.D.) ; ø 16(O.D.)
- (04 - 21) -
IND
OO
R
UN
IT
S
IND
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...