INSTALLATION SPACE
3333
333333 WHEN INSTALL NEAR BY LIMITED HEIGHT WALL
SINGLE AND MULTIPLE INSTALLATIONS
There are no restrictions on the height of the side wall.
●
Provide installation spaces L1 and L2 in accordance with the table below according to the
●
wall height (front side, rear side) conditions.
Provide installation spaces other than L1 and L2 in accordance with the conditions shown in
●
the figure below.
Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
●
larger than 2m.
Wall height condition
Necessary installation space
When H1 is 1500(mm) or less
L1 ≥ 500 (mm)
When H1 is 1500(mm) or more L1 ≥ 500 + h1 ÷ 2 (mm)
When H2 is 500(mm) or less
L2 ≥ 100 (mm)
When H2 is 500(mm) or more
L2 ≥ 100 + h2 ÷ 2 (mm)
Caution
When installing the outdoor unit, pay attention to the following items.
To prevent stopping of operation by short circuit and worsening of performance and high pressure
●
protection, refer to the installation space shown in the figure and secure enough space.
Install in sufficient space considering the carrying in route, installation space, maintenance space,
●
passage of people, etc.
Do not place obstructions in the air flow outlet direction. If there is an obstruction in the outlet
●
direction, install an outlet duct.
When there is a wall in front of the unit, provide a space of 500mm or more as maintenance space.
●
When there is a wall at the left side of the unit, provide a space of 30mm or more as maintenance
●
space.
When installing, also consider the refrigerant piping space.
●
h1
1500
H1
L1
L2
500
h2
H2
L2
L1
L2
L1
<Side view>
<Top view>
30mm or more
30mm or more
20mm or more
20mm or more
10mm or more
10mm or more
<Top view>
Single installation
S
id
e w
al
l
S
id
e w
al
l
S
id
e w
al
l
S
id
e w
al
l
Multiple installations
Front
Rear
Wall
Wall
Front
Front
Rear
Rear
- (03 - 24) -
OU
TD
OO
R
UN
IT
S
OU
TD
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...