6666606 SIGNAL AMPLIFIER
SWITCH POSITION
AUTOMATIC ADDRESS SETTING
Refer to 6-5-7
●
MANUAL ADDRESS SETTING
1) Turn on the power for the signal amplifier.
2) While holding down the set button (SW4), press and release the reset button (SW7) to enter
the address setting mode.
The address setting mode is activated only if the set button is hold down when the reset
button is released.
3) Press the set button (SW4) to display the current address.
The address is set to A1 at the factory.
*1 : When the automatic address setting is selected, the display range is 9 - 16.
4) Press the mode button (SW3) to select the address. *2
The displayed address changes as follows each time the mode button is pressed.
*2 : If connecting multiple signal amplifiers, be sure to select a different address for each amplifier.
If the same address is used for different signal amplifiers, communication cannot occur.
5) Press the set button (SW4) to set the selected address.
6) Turn the power off and on or press the reset button (SW7) to exit the address setting mode
and return to the normal mode.
If an address setting error occurs ("26" is displayed on the right side of the D19 LED
display), the address will not be set. Perform address setting again.
SW3
SW4
SW7
SW2
SW1
D19
D9
D14
D19
D19
D19
D19
A1
A2
A8
A3
A7
A4
A6
A5
*1
For automatic
address setting
D19
Ex.) Address No.5 is selected.
Normal mode
D19
Address setting error
D19
- (06 - 136) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...