WORK FLOW (EXAMPLE)
Prepare schedule of works
Refrigerant check
Refrigerant piping work
Drain piping work
Duct work
Insulation work
Electric wiring work
Outdoor unit foundation work
Outdoor unit installation
Address setting
Leak pressure test
Vacuum evacuation and drying
Refrigerant additional charging
Gas leakage check
Outside panel installation
Test run and adjustment
Hand over
Customer guidance
Refrigerant piping connection (Outdoor unit)
Remote controller installation
Operation chart preparation
Indoor unit installation
Always check the refrigerant to be used.
●
Always use the specified refrigerant.
●
Prepare materials / tools matched to the refrigerant.
●
Air purging by refrigerant gas is strictly prohibited.
●
Use a special vacuum pump with reverse check mechanism.
●
Seal with nitrogen up to 4.2 MPa.
●
After 24 hours, check wether the pressure in piping has not
●
descended.
Calculate the refrigerant additional charging amount, and
●
charge a suitable amount. (Using a special R410A gauge
manifold and charging hose.)
Do not connect to the power source.
●
Use copper tube of the specified material and thickness to
●
meet endurance pressure of the pipe. (4.2 MPa)
Do not use pipe with dust and dirt sticking to it during piping
●
connection work.
Always flow nitrogen during welding work.
●
Preparations
Start of work
- (06 - 14) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...