INSTALLATION
Mounting of indoor unit
z
Please refer to the installation manual provided with the indoor unit for mounting.
●
Please refer to the diagram below for installation height.
●
When installing this product to existing indoor units, please adjust the installation height of the
●
indoor units to height 230-235mm.
Installation of the fresh air intake kit
z
CAUTION
Installing the Fresh Air Intake Kit with the wrong direction is a cause of water leakage.
Provisionally attach the “DRAIN”, “PIPE” of the Fresh Air Intake Kit to the indoor unit foam-
●
sealed “DRAIN”, “PIPE”, following the direction of the indoor unit, using the metal fittings of
the combined diagram.
230 - 235
Indoor unit
Fresh air intake kit
Metal hanging fastener
(Unit : mm)
Ceiling
Metal fittings x 2
"DRAIN"
"DRAIN"
"PIPE"
"PIPE"
Bolt x 4
- (06 - 197) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...