TRANSMISSION LINE SEPARATION RULES
The transmission line between indoor unit, outdoor unit and controllers can be connected by
●
one cable.
Terminal board available on the market or the ones inside the indoor unit or outdoor should
●
be used for transmission line separation.
Connection of three or more lines may cause poor communication for one terminal. In this
●
case, please use a terminal box.
Example 1 : Connecting each outdoor and indoor unit with one connection wiring.
Example 2 : Separating transmission line.
Note
Do not loop.
●
Refrigerant
system 1
Separate on
the terminal for
transmission line.
Separate using
terminal board
System
controller
Refrigerant
system 2
Refrigerant
system 3
Refrigerant
system 1
Refrigerant
system 2
Refrigerant
system 3
Signal
Amplifier
- (06 - 60) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...