667656 INDOOR UNIT
(Wall Mounted type)
CONTROL INPUT
(Start / Stop or Emergency stop)
Indoor unit can be Start/Stop or Emergency stop by using indoor unit PCB CN21.
●
"Start/Stop" mode or "Emergency stop" mode can be selected with function setting of indoor
●
unit.
A twisted pair cable(22AWG) shoud be used. Maximum length of cable is 25m.
●
The wire connection should be separate from the power cable line.
●
Open circuit voltage : ≤ 5.25 (V).
●
Short circuit current : ≤ 0.6 (mA).
●
Short circuit detection resistance (R
●
ON
) : ≤ 500 (ohm).
Open circuit detection resistance (R
●
OFF
) : ≥ 100 (kilo-ohm).
Input signal type
z
Dip-sw [Set 2-1]
Input signal type
OFF
Edge
ON
Pulse
When function setting is "Start/Stop" mode
z
In the case of "Edge" input
●
Connector
Input signal
Command
Ch1 of
CN21
OFF → ON
Operation
ON → OFF
Stop
In the case of "Pulse" input
●
Connector
Input signal
Command
CN21
Ch1
OFF → ON
Operation
Ch2
OFF → ON
Stop
Ch1 input of
CN21
Remote
Controller
Indoor unit
Operation
On
On
Off
Stop
1
2
3
Ch 1
CN21
connected unit
P.C.B
1
2
3
Ch 2
Ch 1
CN21
connected unit
P.C.B
Operation
On
On
The width of pulse must be longer than 200msec.
Off
Off
Stop
CN21
Ch1 input
Ch2 input
NOTE :
The last command has priority.
●
The indoor units within the same remote controller group operates in the same mode.
●
- (06 - 155) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...