OUTPUT
Connector
Output voltage
Status
CN8
12V
Operation
0V
Stop
Output voltage : Hi DC12V ± 2V
Lo 0V
Permissible current : 15mA
A twisted pair cable (22AWG) shoud be used. Maximum length of cable is 25m.
Operation status
●
The output for CN8 is ON when the indoor unit is operating.
The output is off when the unit is stopped.
PARTS
Following cord (service parts) is required. Please use the parts number shown below to
order the cord from your sales representative.
Usage
Name and shapes
Q'ty
Parts No.
For output port
External
input wire
1
9368778002
For control input port
External
input wire
1
9368779009
*If the external indicator has malfunction, due to noise please insert a ceramic capacitor
(0.1μF 25V or more) near the input port of the equipment.
Operation
Stop
12V
0V
CN8
Output
Indoor unit
1
2
+
-
Operation
indicator
CN8
(White)
connected unit
P.C.B
1
2
+
-
Indicator
connected unit
P.C.B
- (06 - 154) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...