SPECIFICATIONS
3333
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
333333 SPACE SAVING COMBINATION
Nominal system capacity
HP
8
10
12
Model name
AJ
A72LALH
AJ
A90LALH
AJ
108LALH
Power source
3N ~ 400 V, 50Hz
Available voltage range
342 to 456V
Capacity
Cooling
kW
22.4
28.0
33.5
Heating
25.0
31.5
37.5
Input power
Cooling
kW
5.51
7.73
9.62
Heating
5.72
7.83
9.28
EER
Cooling
W / W
4.07
3.62
3.48
COP
Heating
4.37
4.02
4.04
Fan
Type x Quantity
Propeller fan x 1
Airflow rate High
m
3
/ h
11,100
11,100
11,100
External static pressure
(Max)
Pa
80
80
80
Motor
Type x Quantity
DC motor × 1
Output
W
600
600
600
Sound pressure
level
Cooling
dB(A)
56
58
58
Heating
58
59
60
Heat exchanger
Length
mm
1,750
1,750
1,750
Fin pitch
1.45
1.45
1.45
Rows x Stages
3 x 60
Face area
m
2
2.2
2.2
2.2
Pipe type (Material)
Grooved H-pin (Copper)
Fin
Type (Material)
Corrugate (Aluminium)
Surface treatment
Corrosion resistance (Blue fin)
Compressor
Type x Quantity
Rotary(inv) x 1
Rotary(inv) x 1
Rotary(inv) x 1
Scroll x 1
Motor output
kW
3.9
3.9
3.9 + 4.5
Crankcase heater
W
25
25
25 + 35
Refrigerant
Type
R410A
Charge
kg
11.2
11.2
11.8
Refrigerant oil
Type
PVE
Enclosure
Material
Painted galvanized steel
Colour
Beige (10YR 7.5/1.0NN)
Dimensions
(H x W x D)
Net
mm
1,690 × 930 × 765
1,690 × 930 × 765
1,690 × 930 × 765
Gross
1,811 × 1,002 × 928 1,811 × 1,002 × 928 1,811 × 1,002 × 928
Weight
Net
kg
220
220
275
Gross
248
248
303
Connection pipe
Pipe
diameter
Liquid
mm
12.70
12.70
12.70
Gas
22.22
22.22
28.58
Method
Liquid
Brazing
Gas
Brazing
Max. length
m
150
Max. height difference
50 / 40 (Outdoor unit : Upper / Lower)
Operation temper-
ature range
Cooling
°CDB
-15 to 46 *1
Heating
-20 to 21
Defrost method
Reversed cycle
Compressor capacity control (Steps / Range)
71 Steps / 30 - 100%
127 Steps / 19 - 100%
Connectable indoor units
Number
15
16
17
*1 : In case of use multiple outdoor units : -5 to 46°C
- (03 - 01) -
OU
TD
OO
R
UN
IT
S
OU
TD
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...