(Unit : mm)
Caution
The connection position is 1/2-20UNF (5/16”) male flare (with valve core).
●
Using a 1/2-20UNF (5/16”) female flare (with valve core) R410A refrigerant charge hose, capillary
●
tube, etc. (something that can amply withstand a pressure of 5MPa), fasten while being careful that
unreasonable stress is not applied to the pressure gauge and the base of the connection piping. At
this time, pump down the inside of the hose to a vacuum.
Connect positively so that there is no refrigerant leakage after installation.
●
PRESSURE GAUGES (RECOMMENDED)
PRESSURE GAUGE MOUNTING PLATE
PRESSURE GAUGE PIPE CONNECTION POSITIONS
Connect each pressure gauge with the pipe at the connection position shown in the figure.
Caution
Use a pressure gauge having an outside diameter (including the
●
mounting part) of ø98 or less and a gauge diameter of ø75 or less
Measuring ranges of the pressure gauges:
●
High-pressure side: 0 to 5 MPa
Low-pressure side: 0 to 3.5 MPa
However, it is recommended that both pressure gauges should
be designed for a measuring range 0 to 5 MPa
Caution
Use a pressure gauge mounting plate of the above outside dimensions.
●
The mounting plate must be thick enough to endure the weights of the pressure gauges.
●
Make mounting screw holes in accordance with each pressure gauge.
●
Each pressure gauge must be installed at the center position shown above
●
Center positions
Pipe connection position
(Piping for the high-pressure side)
Pipe connection position
(Piping for the low-pressure side)
- (03 - 55) -
OU
TD
OO
R
UN
IT
S
OU
TD
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...