Feature
Support
Remark
System
specification
Max. System Controller per VRF Network
1
Max. VRF network supported
4
Site with up to 4 VRF network may be
administered with 1 System Controller
Max. indoor units / remote controller groups
per VRF network
400
Max. indoor units / remote controller groups
per System Controller
1,600
4 VRF networks
Control
Start/Stop, Operation mode, Room
temperature
z
Fan speed, Louver
z
Economy
z
Antifreeze
z
RC prohibition
z
Temperature limit
z
Filter sign reset
z
Memory operation
z
Usability
Quick Control
z
Tool bar provided
Control from layout view
z
Control from list view
z
Control from tree view
z
User defined
group
Number of groups
1,600
Group in group
3 Level
Lv.1 – 2 – 3
Max. overlap definition
1,600
1 unit may belong to up to 1,600 groups
Auto generation
z
By site, building and floor
Status view
3D graphical layout view
z
By site, building or floor
List view
z
Tree view
z
Arranged by groups
Status
Monitoring
Controlled Status
z
See “Control”
Special operation
z
Defrost, Oil Recovery
Scheduled
control
Annual schedule
z
Week of year, day of month, day of
week setting.
Holiday, special day setting
z
Silent mode (weekly)
1
z
Outer unit control only.
Alarm
Supervision
Real time alarm notification
z
Audible alarm
z
E-mail Notification
z
Logging
Operation Data
1 year
Alarm History
1 year
Electricity
Charge
Apportionment
Tenants
50
Power meter interface support
1
20
Bill issuing
z
Charge duration
1 year
Remote
Connection
Max. client connection per server
5
Max. host connection from client
10
Data encryption
z
Support
Function
Unit search by condition
1
z
Search by operation time, etc.
Real time event monitor
1
z
On/Off, temp. out of range event etc.
Database import / export
z
Layout data import/export
z
User Control
z
Authorization level setting
Remote Controller Time Setting
1
z
For wired remote controller, etc
SPECIFICATION SUMMARY
1 :
Scheduled to be offered as options.
- (05 - 15) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...