663656 EV KIT
EV KIT SELECTION
Model name
Application indoor units
UTR-EV09XB
AS
E07LACH, AS
E09LACH
UTR-EV14XB
AS
E12LACH, AS
E14LACH
A wrong selection could cause improper operation, because the built-in electronic expansion
valve is different.
MODELS REQUIRE EV KIT :
AS
E07LACH, AS
E09LACH, AS
E62LACH, AS
E64LACH
Select the above indoor unit for use in small and, quiet rooms such as hotel or bedroom,
●
where noise would be a distraction.
The other indoor units, do not require an EV kit.
●
DECIDING INSTALLATION LOCATION
Keep the installed piping and wiring length less than 5m.
●
EV kit should be considered to install away from the living quarters, such as above the ceiling.
●
Install the EV kit where it can be accessed for servicing.
●
An EV kit must be required for the compact wall mounted type (EEV
external model) on the liquid pipe side6
CAUTION
Do not install EV kit in a location with any of the following conditions.
Do not install the kit outdoor.
●
Do not install the kit where the danger of combustible gas leakage.
●
Do not install the kit where near a fire place or other heating appartatus.
●
Do not install the kit where oily smoke, machine oil (i.e. factory),salty enviloment with
●
direct sea breeze.
Do not install the kit where too much of dust.
●
Do not install the kit where corrosive gas such as sulphurous acid gas is generated.
●
Do not install the kit where exposed to rains and direct sunlight.
●
EV Kit
Service hole
Indoor unit
5m : Max. (wiring length)
Ceiling
- (06 - 47) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...