Selection of pipe size
z
a
b
c
d
e
f *
f1
g
h1
h2
Liquid pipe
12.70
12.70
12.70
15.88
19.05
19.05
9.52
12.70
9.52
12.70
Gas pipe
28.58
28.58
22.22
28.58
34.92
34.92
19.05
28.58
19.05
22.22
Length (m)
Example
2
2
2
2
40
10
10
5
5
10
i
j1
k1
l1
m1
n1
Liquid pipe
15.88
9.52
9.52
9.52
9.52
9.52
Gas pipe
28.58
19.05
19.05
19.05
19.05
19.05
Length (m)
Example
20
10
5
10
5
10
Pipe size "f" selection : Even though this pipe size might be selected based on downstream
*
cooling capacity (95.9kW) 19.05 / 41.27, This pipe size should not be larger than pipe size "e".
Therefore select pipe size equal to pipe size "e" (19.05 / 34.92).
Calculation of additional charge refrigerant
z
66 Calculation of additional amount for outdoor unit
Model
Additional amount for
outdoor unit (kg)
Outdoor unit1
AJ
126
3.30
Outdoor unit2
AJ
108
1.20
Outdoor unit3
AJ
A72
0
A = 3630 + 6620 + 0 = 4650 (kg)
26 Calculation of additional amount for pipe length
Liquid pipe size
19.05
15.88
12.70
9.52
6.35
Additional refrigerant
(kg/m)
0.268
0.178
0.114
0.058
0.021
Liquid pipe length (m)
50
22
21
55
0
B = (06268 x 50) + (06678 x 22) + (06664 x 26) + (06058 x 55) = 22690 kg
36 Calculation of additional charge refrigerant
C = A + B = 4650 + 22690 = 27640 (kg)
46 Calculation of factory charged amount
Model
Factory charged
amount (kg)
Outdoor unit1
AJ
126
11.80
Outdoor unit2
AJ
108
11.80
Outdoor unit3
AJ
A72
11.20
D = 66680 + 66680 + 66620 = 34680 (kg)
56 Total refrigerant amount check
E = C + D = 27.40 + 34.80 = 62.20 (kg) < 94.5 (kg) → OK
Check pipe length and height difference between units by comparing with items shown in "6-2-2.
LIMITATION".
- (06 - 30) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...