Heat insulation installation
z
After brazing the pipes, and leak check use the supplied insulation to insulate them.
1) Remove the protective sheet from the double-stick that is affixed to the heat insulation.
2) Be sure to fix each insulation at 4 positions with tape (accessory) in the following figure.
3) Seal the connection part with tape to avoid any gap.
CAUTION
Insulate the liquid and gas pipe completely. If not, it may cause the water condensaton or performance reduction.
●
Wrap the heat insulation with tape or pipe cover in order to extend the life time of heat insulation.
●
Take proper measurement to strenghten by using another heat insulation at the following installing enviroment
●
(a) Environment temperature ≥ 35°C and humidity 85%.
(b) Environment temperature ≥ 25°C and humidity 90%.
Keep the distance 0.5m or more for straight part to separation tube, in order to prevent the outdoor
unit mulfunction and generation of refrigerant noise
Caution
2) Straight pipe length
A straight pipe (minimum lenght 0.5m) before separation tube is necessary in order to
separation the rifregerant exactly.
Insulation (locally procured)
Insulation (locally procured)
Contact each other
Contact each other
Contact each other
Tape (locally procured) Tape (locally procured)
Tape (locally procured)
Installation example
Heat insulation (locally procured)
Main pipe
0.5m or more
0.5m or more
To indoor unit
To indoor unit
To indoor unit or to
separation tube or
to header
To indoor unit or to
separation tube or
to header
To indoor unit
- (06 - 43) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...