![Fujitsu AIRSTAGE V-II Design & Technical Data Download Page 233](http://html.mh-extra.com/html/fujitsu/airstage-v-ii/airstage-v-ii_design-and-technical-data_118213233.webp)
333323 WHEN INSTALL NEAR BY UNLIMITED HEIGHT WALL
SINGLE AND MULTIPLE INSTALLATIONS
There are no restrictions on the height of the wall.
●
The wall (without height restrictions) must not exist on the both sides (left / right) of outdoor
●
unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
Provide installation spaces other than L6 in accordance with the conditions shown in the
●
figure below.
Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
●
larger than 2m.
When installing with the REAR of the outdoor unit facing the wall side
z
Condition
Necessary installation space
When B ≥ 400 (mm)
L6 ≥ 200 (mm)
When 20 ≤ B < 400 (mm)
L6 ≥ 200 + (400 - B) x 3 (mm)
When installing with the FRONT of the outdoor unit facing the wall side
z
Front
Rear
<Top view>
200mm
or more
800mm
or more
200mm
200mm
Front
Wall
Wall
Wall
Wa
ll
Wa
ll
Wa
ll
Front
Rear
Rear
<Top view>
<Top view>
L6
200mm
or more
100mm
or more
200mm
or more
B
B
Single installation
Multiple installations
Example :
When B is made 200mm
L6 ≥ 200+(400-200)x3=800mm
Front
Front
Rear
Rear
<Top view>
<Top view>
200mm
or more
200mm
or more
20mm
or more
20mm
or more
500mm
or more
500mm
or more
Wall
Wall
Wa
ll
Wa
ll
- (03 - 26) -
OU
TD
OO
R
UN
IT
S
OU
TD
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...