(Unit : mm)
INSTALLATION PLACE
MAINTENANCE HOLE
WHEN USING A SQUARE DUCT
500mm or more
1550mm or more
400mm or more
300mm
or more
300mm
or more
150mm or more
Service space
Service hole
500mm
or
more
500mm
or
more
100mm
100mm
Strong and durable ceiling
Ii shall be possible to install and remove
the control box.
Ii shall be possible to install and remove
the control box, fan units and filter.
1 When drain pump is used, leave the
space required for service and
maintenance (Refer to 6-10-1. DRAIN
PUMP UNIT)
2 When drain hose is connected, the
required dimension is 400mm or more.
1
2
- (04 - 33) -
IND
OO
R
UN
IT
S
IND
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...