Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
442444 LOW STATIC PRESSURE DUCT TYPE
Model name
ARXB24LATH
ARXB30LATH
ARXB36LATH
ARXB45LATH
Power source
230V ~, 50Hz
Available voltage range
198 to 264 V
Capacity
Cooling
kW
7.1
9.0
11.2
12.5
Heating
8.0
10.0
12.5
14.0
Input power
W
145
198
253
338
Static pressure range
Pa
0 to 80
Standard static pressure
Pa
40
50
50
60
Fan
Airflow rate
High
m
3
/ h
1,100
1,410
1,710
1,970
Med
920
1,280
1,600
1,790
Low
810
1,150
1,470
1,670
Type x Quantity
Sirocco ×2
Motor output
W
63
90
90
176
Sound pressure
level
High
dB(A)
31
34
37
41
Med
27
32
35
38
Low
25
29
33
36
Heat exchanger Length
mm
1,000
Fin pitch
1.40
Rows x Stages
3 × 14
4 × 14
Face Area
m
2
0.29
Pipe type (Material)
Grooved H-pin (Copper)
Fin
Type (Material)
Slit(Aluminium)
Surface
treatment
Hydrophilic coating
Air filter (Option) Model name
UTD-LF25NA
Type
Fungicide type
Net material
PP honeycomb
Enclosure
Material
galvanized sheet iron
Colour
-
Dimensions
(H x W x D)
Net
mm
270 × 1,135 × 700
Gross
300 × 1,320 × 790
Weight
Net
kg
43
45
Gross
50
52
Connection
pipe diameter
Liquid (Flare)
mm
ø 9.52
Gas (Flare)
ø 15.88
ø 19.05
Drain
ø 25(I.D.) ; ø 32(O.D.)
- (04 - 14) -
IND
OO
R
UN
IT
S
IND
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...