33303 LOCALLY PROCURED PARTS
3330333 AIR DISCHARGE DUCT
PRECAUTION
All the components/parts such as the duct, frame, and screws are to be locally procured.
●
Do not install the duct where seasonal wind blow directly against to the discharge port.
●
Install so that the static pressure of the air flow path
●
, including the duct is 80Pa or less.
Note that installation of the duct increases the height of the cabinet.
●
If installation space may narrow, like as consecutive unit layout, be sure to fix the duct to the
●
unit before placing the unit.
When the duct is installed, the noise may become louder.
●
DUCT LAYOUT EXAMPLE
Model
Dimension C
(Minimum)
(Maximum)
AJ
A72LALH
862
928
AJ
A90LALH
AJ
108LALH
AJ
126LALH
1172
1238
AJ
144LALH
Caution
Make the height A of the duct opening section 500mm or greater.
●
Make the height B of the duct, excluding the flange 500mm or greater.
●
Make the width (dimension C) of the duct within the range of the table shown above.
●
Provide a Chamfer or round the corner at the air flow path.
●
Design the duct weight with 100kg or less as the standard.
●
Design the duct so that maintenance of the motor is possible.
●
When the length of the duct is long, provide support material at suitable intervals.
●
500
500
114
1576
Chamfer or a round the corner
- (03 - 49) -
OU
TD
OO
R
UN
IT
S
OU
TD
OO
R
UN
IT
S
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...