667626 INDOOR UNIT
(Compact Cassette type and Cassette type)
CONTROL INPUT
(Start / Stop or Emergency stop)
Indoor unit can be Start/Stop or Emergency stop by using indoor unit PCB CN6 or CN17.
●
"Start/Stop" mode or "Emergency stop" mode can be selected with function setting of indoor
●
unit.
A twisted pair cable (22AWG) shoud be used. Maximum length of cable is 150m.
●
The wire connection should be separate from the power cable line.
●
Input select
z
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
Voltage terminal ([CN6])
●
When a power supply must be provided at the input device you want to connect, use the
voltage terminal ([CN6])
No voltage terminal ([CN67])
●
When a power supply is unnecessary at the input device you want to connect, use the no
voltage terminal ([CN17]).
1
2
3
+
+
-
-
-
In
pu
t d
ev
ic
e 1
In
pu
t d
ev
ic
e 2
Load
resistance
Load
resistance
*9
DC power
supply 12 - 24V
connected unit
P.C.B
CN6
*a
*a
*b
*9: Make the power supply DC12 to 24V. Select a power supply capacity with an ample surplus for the
connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a: The allowable current is DC10mA or less. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b: The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
*c: Select very low current use contacts (usable at DC12V, DC1mA or less).
*d: The wiring is different from voltage terminals. Be sufficiently careful when wiring.
1
2
3
P.C.B
GND
Ch 1
*c
*c
*d
Ch 2
CN17
connected unit
- (06 - 144) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...