![Fujitsu AIRSTAGE V-II Design & Technical Data Download Page 633](http://html.mh-extra.com/html/fujitsu/airstage-v-ii/airstage-v-ii_design-and-technical-data_118213633.webp)
OUTPUT
Connector
Output voltage
Status
CN410
(Black)
Ch1
0V
All of indoor units "Stop"
Pins1-2
DC12V *17
At least one more indoor units "Operation"
Ch2
0V
Normal
Pins3-4
DC12V *17
Error
Operation status (External output6)
●
The output for CN410(1-2) is ON when at least one more indoor units is operating.
The output is OFF when all of indoor units is stopped.
Error status (External output2)
●
The output for CN410(3-4) is ON when Error of at least one more indoor or outdoor units is
generated.
PARTS
Following cord (service parts) is required. Please use the parts number shown below to
order the cord from your sales representative.
Name and shapes
Q'ty
Parts No.
External
output wire
1
9379529006
CN410(1-2)
Output
Indoor
units
Operation
Stop
12V
0V
CN410(3-4)
Output
Indoor units or
Outdoor units
Error
Normal
12V
0V
1
2
3
4
P.C.B
CN410
(Black)
Connected load
*18
connected unit
Connected load
*18
DC power supply
12V
+
+
+
+
-
-
-
-
*19
*17: Provide a DC12V power supply. Select a
power supply capacity with an ample surplus
for the connected load.
Do not impress a voltage exceeding 12V
across pins 1-2, and 3-4
*18: The allowable current is DC15mA or
less. Provide a load resistance such that the
current becomes DC15mA or less.
*19: Polarity is [+] for pins 1,3 and [-] for pins
2-4.
- (06 - 161) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...