6666636 ADMINISTRATIVE INDOOR UNIT SETTING
An indoor unit which decides the priority mode (cooling or heating) in a same refrigerant
●
system.
“Administrative Indoor Unit” can be set to a unit in a same refrigerant system.
●
SETTING METHOD
Outdoor unit function setting
z
Please set to "Priority given to administrative indoor unit" with function setting of outdoor
unit. →Refer to 6-6-1.OUTDOOR UNIT
Wired remote controller setting
z
(1) After the indoor unit stops operation, press the “MODE” button of wired remote controller
for 5 seconds continuously.
The operating mode of the wired remote controller display lights on after 5 seconds as
follows.
(2) Press the “MODE ” button.
Display (1)-b) when setting, and display (1)-a) when releasing.
→ The display blinks when the “MODE ” button is pressed, and the display of (1)-a) and (1)-b)
alters whenever the “MODE ” button is pressed.
→ The contents set in the wired remote controller are transferred to the indoor unit
immediately after the display is selected. It may take 10 seconds depending on
communication conditions. While this period, the button operation will be suspended.
→ It returns to the normal display after 20 seconds automatically if the operation button is
not pressed.
→ When setting or releasing is completed, the indication on wired remote controller changes
to the normal indication from blinking.
(3) Complete the setting or releasing of “Administrative Indoor Unit”.
Press the “MODE ” button of the wired remote controller again for 5 seconds continuously.
→ The indication returns to normal display if the “MODE” button is pressed for 5 seconds
continuously.
(It returns to normal indication after 20 seconds even if the “MODE ” button is not pressed.)
(1)-a) The indication not
set as "Administrative
indoor unit"
(1)-b) The indication
set as "Administrative
indoor unit"
Note
“MODE ” button is locked by below reasons while the marking lights on.
●
In such case, “Administrative Indoor Unit” cannot be set or released.
“Priority on Administrative Indoor Unit” is not selected in
●
the setting of priority mode of outdoor unit.
→Set “Administrative Indoor Unit” in the wired remote controller after selecting “Priority on
Administrative Indoor Unit” in setting of priority mode of outdoor unit.
Another indoor unit was set to “Administrative Indoor Unit” already.
●
→Release the setting “Administrative Indoor Unit” of another indoor unit.
Operation Lock Display
- (06 - 141) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AIRSTAGE V-II
Page 10: ...1 GENERAL INFORMATION ...
Page 32: ...2 MODEL SELECTION ...
Page 207: ...3 OUTDOOR UNITS ...
Page 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Page 265: ...4 INDOOR UNITS ...
Page 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Page 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Page 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Page 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Page 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Page 388: ...5 CONTROL SYSTEM ...
Page 472: ...6 SYSTEM DESIGN ...
Page 694: ...7 OPTIONAL PARTS ...