P2.2.6.6
Scaling of generator torque limit
0
5
-
0
1087
As parameter P2.2.6.1
P2.2.6.7
Scaling of motoring power limit
0
5
-
0
179
P2.2.6.8
Scaling of generator power limit
0
5
-
0
1088
Table 62: Digital Inputs (Control Panel: Menu M2 -> G2.2.4)
Index
Parameter
Min Default ID
Description
P2.2.7.1
(1)
Start signal 1
0.1
A.1
403
See P2.2.1.1.
P2.2.7.2
(1)
Start signal 2
0.1
A.2
404
See P2.2.1.1.
P2.2.7.3
(1)
Run enable
0.1
0.2
407
-
P2.2.7.4
(1)
Reverse
0.1
0.1
412
-
P2.2.7.5
(1)
Preset speed 1
0.1
0.1
419
See preset speeds in Basic Parameters (G2.1).
P2.2.7.6
(1)
Preset speed 2
0.1
0.1
420
P2.2.7.7
(1)
Preset speed 3
0.1
0.1
421
P2.2.7.8
(1)
Motor potentiometer reference DOWN 0.1
0.1
417
-
P2.2.7.9
(1)
Motor potentiometer reference UP
0.1
0.1
418
-
P2.2.7.10
(1)
Fault reset
0.1
A.3
414
-
P2.2.7.11
(1)
External fault 1 (close)
0.1
A.5
405
-
P2.2.7.12
(1)
External fault 2 (open)
0.1
0.2
406
-
P2.2.7.13
(1)
Acc/Dec time selection
0.1
A.6
408
-
P2.2.7.14
(1)
Acc/Dec prohibit
0.1
0.1
415
-
P2.2.7.15
(1)
DC braking
0.1
0.1
416
-
P2.2.7.16
(1)
Jogging speed
0.1
A.4
413
-
P2.2.7.17
(1)
AI1/AI2 selection
0.1
0.1
422
-
P2.2.7.18
(1)
Control from I/O terminal
0.1
0.1
409
-
P2.2.7.19
(1)
Control from keypad
0.1
0.1
410
-
P2.2.7.20
(1)
Control from fieldbus
0.1
0.1
411
-
P2.2.7.21
(1)
Parameter set 1/set 2 selection
0.1
0.1
496
-