Table 122: Current Scaling in Different Size of Units
Voltage (V AC)
Size
Scale
208–240
NX_2 0001–0011
100 – 0.01 A
208–240
NX_2 0012–0420
10 – 0.1 A
380–500
NX_5 0003–0007
100 – 0.01 A
380–500
NX_5 0009–0300
10 – 0.1 A
380–500
NX_5 0385 –
1–1 A
525–690
NX_6 0004–0013
100 – 0.01 A
525–690
NX_6 0018 –
10 – 0.1 A
10.624.3 Process Data in (Master -> Slave)
ControlWord, Reference, and Process Data are used in All in One applications as follows:
Table 123: Basic, Standard, Local/Remote, Multi-Step Applications
Data
Value
Unit
Scale
Reference
Speed reference
%
0.01%
ControlWord
Start/Stop command
Fault reset command
-
-
PD1 – PD8
Not used
-
-
The settings in
are factory defaults. See also parameter group
G2.9
.
Table 124: Multi-Purpose Control Application
Data
Value
Unit
Scale
Reference
Speed reference
%
0.01%
ControlWord
Start/Stop command
Fault reset command
-
-
Process Data IN1
Torque reference
%
0.01%
Process Data IN2
Free analog input
%
0.01%
Process Data IN3
Adjust input
%
0.01%
PD4 – PD8
Not used
-
-
Table 125: PID Control and Pump and Fan Control Applications
Data
Value
Unit
Scale
Reference
Speed reference
%
0.01%
ControlWord
Start/Stop command
Fault reset command
-
-
Process Data IN1
Reference for PID controller
%
0.01%
AB296635287482en-000301 / DPD00903
310 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX