10.542 (ID 3508) Modified Value
Location in the menu:
P2.13.2.7
(Multi-purpose Control Application)
Use this parameter to give new value to the point selected with
ID 3507
.
10.543 (ID 3509) Baseline Data Selector
Location in the menu:
P2.13.2.9
(Multi-purpose Control Application)
Use this parameter to select which array points can be monitored in monitor group
M1.24.1 Baseline data
.
10.544 (ID 3511) Current Mean Factor
Location in the menu:
P2.13.3.3.1
(Multi-purpose Control Application)
The several statistical data points (mean, minimum, maximum, and standard) from the baseline model can be combined into one
threshold value. Use this parameter to set the mean factor in the threshold value. If the threshold value is zero, the mean factor is
not used.
Threshold value = MeanFactor
∗
mean + MinFactor
∗
min + MaxFactor
∗
max + StdFactor
∗
stddev
10.545 (ID 3512) Current Min Factor
Location in the menu:
P2.13.3.3.2
(Multi-purpose Control Application)
The several statistical data points (mean, minimum, maximum, and standard) from the baseline model can be combined into one
threshold value. Use this parameter to set min factor in the threshold value. If the threshold value is zero, the min factor is not used.
See the formula in
10.544 (ID 3511) Current Mean Factor
.
10.546 (ID 3513) Current Max Factor
Location in the menu:
P2.13.3.3.3
(Multi-purpose Control Application)
The several statistical data points (mean, minimum, maximum, and standard) from the baseline model can be combined into one
threshold value. Use this parameter to set the max factor in the threshold value. If the threshold value is zero, the max factor is not
used.
See the formula in
10.544 (ID 3511) Current Mean Factor
.
10.547 (ID 3514) Current Std Factor
Location in the menu:
P2.13.3.3.4
(Multi-purpose Control Application)
The several statistical data points (mean, minimum, maximum and standard) from the baseline model can be combined into one
threshold value. Use this parameter to set the std factor in the threshold value. If the threshold value is zero, the std factor is not
used.
See the formula in
10.544 (ID 3511) Current Mean Factor
.
10.548 (ID 3515) Current Interpolation Type
Location in the menu:
P2.13.3.3.5
(Multi-purpose Control Application)
Use this parameter to select interpolation type for the notification threshold values across frequency points.
ValueN
Value2
Value1
Value0
Threshold
Value
Frequency
f2
f1
f0
fN
e3
0b
i5
56
.1
0
Illustration 95: Current Interpolation Type
10.549 (ID 3516) Current Warning S1 Mode
Location in the menu:
P2.13.3.4.1
(Multi-purpose Control Application)
Use this parameter to select the warning S1 mode which is used for calculating warning S1 notification threshold.
AB296635287482en-000301 / DPD00903
296 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide