Index
Parameter
Min
Max
Unit Default ID
Description
2 = High limit
P2.3.21
Frequency converter tempera-
ture limit value
-10
100
°C
40
355 -
P2.3.22
Analog output 2 scaling
0.1
E.10
-
0.1
471 -
P2.3.23
Analog output 2 function
0
8
-
4
472 As parameter 2.3.2
P2.3.24
Analog output 2 filter time
0.00
10.00
s
1.00
473 0 = No filtering
P2.3.25
Analog output 2 inversion
0
1
-
0
474 0 = Not inverted
1 = Inverted
P2.3.26
Analog output 2 minimum
0
1
-
0
475 0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.27
Analog output 2 scaling
10
1000
%
1.00
476 -
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
.
4.4.5 Drive Control Parameters (Control Panel: Menu M2->G2.4)
Table 19: Drive Control Parameters, G2.4
Index
Parameter
Min Max
Unit Default ID
Description
P2.4.1
Ramp 1 shape
0.0
10.0
s
0.1
500 0 = Linear
100 = full acc/dec inc/dec tmes
P2.4.2
Ramp 2 shape
0.0
10.0
s
0.0
501 0 = Linear
100 = full acc/dec inc/dec tmes
P2.4.3
Acceleration time 2
0.1
3000.0 s
1.0
502 -
P2.4.4
Deceleration time 2
0.1
3000.0 s
1.0
503 -
P2.4.5
Brake chopper
0
4
-
0
504 0 = Disabled
1 = Used when running
2 = External brake chopper
3 = Used when stopped/running
4 = Used when running (no testing)
P2.4.6
Start function
0
2
-
0
505 0 = Ramp
1 = Flying start
2 = Conditional flying start
P2.4.7
Stop function
0
3
-
0
506 0 = Coasting
1 = Ramp
2 = Ramp+Run enable coast
3 = Coast+Run enable ramp
AB296635287482en-000301 / DPD00903 | 39
Danfoss A/S © 2023.02
Local/Remote Control Application
VACON® NX All-in-One
Application Guide