10.51 (ID 164) Motor Control Mode
Location in the menu:
P2.2.7.22
(Multi-Purpose Control Application)
Use this parameter to set the motor control mode 1 or 2.
Contact is open (oc) = Motor control mode 1 is selected
Contact is closed (cc) = Motor control mode 2 is selected
See parameter
ID 600
and
ID 521
.
Change from open loop to closed loop control modes and the opposite way can only be made in stop state.
10.52 (ID 165) AI1 Joystick Offset
Location in the menu:
P2.2.2.11
(Multi-Purpose Control Application)
Use this parameter to set the frequency zero point. Find the parameter, set the potentiometer at the assumed zero point and press
[enter] on the keypad.
This action will not, however, change the reference scaling.
To change the parameter value back to 0.00%, press the [reset] button.
10.53 (ID 166) AI2 Joystick Offset
Location in the menu:
P2.2.3.11
(Multi-Purpose Control Application)
Use this parameter to set the frequency zero point. Find the parameter, set the potentiometer at the assumed zero point and press
the [enter] button on the keypad.
See parameter
ID 165
.
10.54 (ID 167) PID Reference 1
Location in the menu:
P3.4
(PID Control Application, Pump and Fan Control Application)
Use this parameter to set the reference value of the PID controller.
The PID controller keypad reference can be set between 0–100%. This reference value is the active PID reference if parameter
ID 332
= 2.
10.55 (ID 168) PID Reference 2
Location in the menu:
P3.5
(PID Control Application, Pump and Fan Control Application)
Use this parameter to set the reference value of the PID controller.
The PID controller keypad reference 2 can be set between 0–100%. This reference is active if the DIN 5 function = 13 and the DIN 5
contact is closed.
10.56 (ID 169) Fieldbus DIN 4
Location in the menu:
P2.3.3.27
(Multi-Purpose Control Application)
Use this parameter to connect the Fieldbus signal (FBFixedControlWord) to the digital input of your selection.
10.57 (ID 170) Fieldbus DIN 5
Location in the menu:
P2.3.3.28
(Multi-Purpose Control Application)
Use this parameter to connect the Fieldbus signal (FBFixedControlWord) to the digital input of your selection.
See the fieldbus manual of the used fieldbus for more details.
10.58 (ID 179) Scaling of Motoring Power Limit
Location in the menu:
P2.2.6.7
(Multi-Purpose Control Application)
Use this parameter to set limit to the maximum motor power.
The motoring power limit is equal to
ID 1289
when value 0 'Not used' is selected. If any of the inputs is selected, the motoring power
limit is scaled between zero and parameter
ID 1289
. This parameter is available for VACON
®
NXP closed loop control mode only.
10.59 (ID 214) Active Filter Fault Input
Location in the menu:
P2.2.7.33
(Multi-Purpose Control Application)
Use this parameter to enable Active Filter Fault.
This parameter selects the digital input which triggers active filter fault/warning according to parameter
ID 776
. If the contact is
closed, the response defined by parameter
ID 776
is triggered.
AB296635287482en-000301 / DPD00903
180 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......