10.130 (ID 374) Analog Input Limit Value
Location in the menu:
P2.3.2.15
(Pump and Fan Control Application)
Use this parameter to set the limit supervision value for the selected analog input when activating the limit supervision function.
The parameter
ID 373
supervises the value of the selected analog input.
10.131 (ID 375) Analog Output 1 Offset
Location in the menu:
P2.3.3.7
(Pump and Fan Control Application)
P2.3.5.7
(Multi-purpose Control Application)
Use this parameter to add offset to the analog output 1.
Add -100.0% to 100.0% to the analog output signal.
10.132 (ID 376) PID Sum Point Reference (Place A Direct Reference)
Location in the menu:
P2.2.4
(PID Control Application)
Use this parameter to select extra reference sources to the PID controller output when PID controller is used.
Selection
number
Selection name
Description
0
No additional reference
(Direct PID output value)
1
PID AI1 reference from terminals 2 and 3 (for example, potentiometer) -
2
PID AI2 reference from terminals 4 and 5 (for example, transducer)
-
3
PID PID keypad reference
-
4
PID Fieldbus reference (FBSpeedReference)
-
5
PID Motor potentiometer reference
-
6
PID Fi PID output (ProcessDataIN3)
.
7
PID Motor potentiometer
-
If value 7 is selected for this parameter, the values of parameters
ID 319
and
ID 301
are automatically set to 13.
30.00
20.00
e3
0bh047.1
0
A
D
B
C
Illustration 58: PID sum point reference
A
Frequency
B
PID Maximum limit
C
PID Minimum limit
D
Time
The maximum and minimum limits illustrated in the picture limit only the PID output, no other outputs.
AB296635287482en-000301 / DPD00903 | 211
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide