Table 2: Monitoring Values
Index
Monitoring value
Unit
Form
ID
Description
V1.1
Output frequency
Hz
#.##
1
-
V1.2
Frequency reference
Hz
#.##
25
-
V1.3
Motor speed
RPM
#
2
-
V1.4
Motor current
A
Varies
3
-
V1.5
Motor torque
%
#.#
4
-
V1.6
Motor shaft power
%
#.#
5
-
V1.7
Motor voltage
V
#.#
6
-
V1.8
DC-link voltage
V
#
7
-
V1.9
Unit temperature
°C
#
8
-
V1.10
Motor temperature
%
#.#
9
-
V1.11
Analog input 1
V/mA
#.##
13
-
V1.12
Analog input 2
V/mA
#.##
14
-
V1.13
DIN 1, 2, 3
-
-
15
-
V1.14
DIN 4, 5, 6
-
-
16
-
V1.15
DO1, RO1, RO2
-
-
17
-
V1.16
Analog I
out
mA
#.##
26
-
V1.17
Multimonitoring items
-
-
-
-
2.4.2 Basic Parameters (Control Panel: Menu M2 -> G2.1)
Table 3: Basic Parameters G2.1
Index Parameter
Min
Max
Unit Default
ID
Description
P2.1
Min frequency
0.00
P2.2
Hz
0.00
101 -
P2.2
Max frequency
P2.1
320.00 Hz
50.00
102 -
P2.3
Acceleration time 1
0.1
3000.0 s
3.0
103 -
P2.4
Deceleration time 1
0.1
3000.0 s
3.0
104 -
P2.5
Current limit
0.1 x I
H
2 x I
H
A
I
L
107 -
P2.6
Nominal voltage of the motor
180
690
V
NX2: 230 V
NX5: 400 V
NX6: 690 V
110 -
P2.7
Nominal frequency of the mo-
tor
8.00
320.00 Hz
50.00
111 -
P2.8
Nominal speed of the motor
24
20 000 RPM 1440
112 -
AB296635287482en-000301 / DPD00903 | 13
Danfoss A/S © 2023.02
Basic Application
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......