P2.3.18
(Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application)
P2.3.4.9
(Multi-Purpose Control Application)
P2.3.2.9
(Pump and Fan Control Application)
Use this parameter to set the delay time to open the brake after the conditions to open the brake are filled.
See
10.111 (ID 353) External Brake-On Delay
10.111 (ID 353) External Brake-On Delay
Location in the menu:
P2.3.19
(Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application)
P2.3.4.10
(Multi-Purpose Control Application)
P2.3.2.10
(Pump and Fan Control Application)
Use this parameter to set the delay time to close the brake after the conditions to close the brake are filled.
The function of the external brake can be timed to the start and stop control signals with these parameters. See
10.620 External Brake Control with Additional Limits (IDs 315, 316, 346–349, 352, 353)
The brake control signal can be programmed via the digital output DO1 or via one of the relay outputs RO1 and RO2. See parame-
ters
ID 312
to
ID 314
(Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application) or
ID 445
(Multi-Purpose Control Application, Pump, and Fan Control Application). The brake-on delay is ignored when the unit is reaching a
stop state after a ramp-down or if stopped by coasting.
A
B
t
t
DIN1: RUN FWD
STOP
External
BRAKE: OFF
ON
DO1/RO1/
RO2
DO1/RO1/
RO2
DIN2: RUN REV
STOP
DIN1: START
PULSE
External
BRAKE: OFF
ON
DIN2: STOP
PULSE
t
OFF
=ID352
t
ON
=ID353
t
OFF
=ID352
t
ON
=Par. ID353
e
3
0
b
h
0
4
1
.1
0
Illustration 49: External Brake Control
A
Start/Stop logic selection, ID 300 = 0, 1 or 2
B
Start/Stop logic selection, ID 300= 3
10.112 (ID 354) Frequency Converter Temperature Limit Supervision
Location in the menu:
P2.3.20
(Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application)
P2.3.4.11
(Multi-Purpose Control Application)
P2.3.2.11
(Pump and Fan Control Application)
Use this parameter to select the limit supervision function for the temperature of the AC drive.
If the temperature of the AC drive unit falls below or exceeds the set limit (
ID 355
), this function generates a message through a
digital output depending on:
the settings of parameters
ID 312
to
ID 314
(Local/Remote Control Application, Multi-Step Speed Control Application, PID Con-
trol Application), or
to which output the temperature limit supervision signal (parameter
ID 450
) is connected (Multi-Purpose Control Application,
Pump and Fan Control Application).
For more information on selection Brake-off control (only in Multi-Purpose Control Application), see
with Additional Limits (IDs 315, 316, 346–349, 352, 353)
AB296635287482en-000301 / DPD00903 | 203