Index Parameter
Min
Max
Unit Default
ID
Description
P2.9
Nominal current of the motor
0.1 x I
H
2 X I
H
A
I
H
113 -
P2.10
Motor cos phi
0.30
1.00
-
0.85
120 -
P2.11
Start function
0
2
-
0
505 0 = Ramp
1 = Flying start
2 = Conditional flying start
P2.12
Stop function
0
3
-
0
506 0 = Coasting
1 = Ramp
2 = Ramp + Run enable coast Ramp
3 = Coast + Run enable ramp
P2.13
U/f optimization
0
1
-
0
109 0 = Not used
1 = Automatic torque boost
P2.14
I/O reference
0
3
-
0
117 0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.15
Analog input 2, reference off-
set
0
1
-
1
302 0 = 0–20 mA
1 = 4–20 mA
P2.16
Analog output function
0
8
-
1
307 0 = Not used
1 = Output freq. (0- f
max
)
2 = Freq. reference (0-f
max
)
3 = Motor speed (0-Motor nominal speed)
4 = Output current (0-InMotor)
5 = Motor torque (0-TnMotor)
6 = Motor power (0-PnMotor)
7 = Motor voltage (0-UnMotor)
8 = DC-link volt (0-1000V)
P2.17
DIN 3 function
0
7
-
1
301 0 = Not used
1 = Ext. fault, closing cont.
2 = Ext. fault, opening cont.
3 = Run enable, cc
4 = Run enable, oc
5 = Force cp. to I/O
6 = Force cp. to keypad
7 = Force cp. to fieldbus
P2.18
Preset speed 1
0.00
P2.2
Hz
0.00
105 -
P2.19
Preset speed 2
0.00
P2.2
Hz
50.00
106 -
P2.20
Automatic restart
0
1
-
0
731 0 = Disabled
2 = Enabled
AB296635287482en-000301 / DPD00903
14 | Danfoss A/S © 2023.02
Basic Application
VACON® NX All-in-One
Application Guide