Index
Parameter
Min Max
Unit Default ID
Description
1 = Inverted
P2.3.5
Analog output minimum
0
1
-
0
310 0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.6
Analog output scale
10
1000
%
100
311 -
P2.3.7
Digital output 1 function
0
16
-
1
312 0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = AC drive overheat warning
6 = Ext. fault or warning
7 = Ref. fault or warning
8 = Warning
9 = Reversed
10 = Preset speed 1
11 = At speed
12 = Motor regulator active
13 = OP freq. limit 1 superv.
14 = Control place: I/O
15 = Thermistor fault/warning
16 = Fieldbus DIN 1
P2.3.8
RO1 function
0
16
-
2
313 As parameter 2.3.7
P2.3.9
RO2 function
0
16
-
3
314 As parameter 2.3.7
P2.3.10
Output frequency limit 1 super-
vision
0
2
-
0
315 0 = No limit
1 = Low limit supervision
2 = High limit supervision
P2.3.11
Output frequency limit 1; Super-
vised value
0.00 320.00 Hz
0.00
316 -
P2.3.12
(1)
Analog output 2 signal selection
0.1
E.10
-
0.1
471 -
P2.3.13
Analog output 2 function
0
8
-
4
472 As parameter 2.3.2
P2.3.14
Analog output 2 filter time
0.00 10.00
s
1.00
473 0 = No filtering
P2.3.15
Analog output 2 inversion
0
1
-
0
474 0 = Not inverted
1 = Inverted
P2.3.16
Analog output 2 minimum
0
1
-
0
475 0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.17
Analog output 2 scaling
10
1000
%
1.00
476 -
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
AB296635287482en-000301 / DPD00903
22 | Danfoss A/S © 2023.02
Standard Application
VACON® NX All-in-One
Application Guide