This parameter is present in VACON
®
NXP drives only.
This input is configured as normally open. If a normally closed input is needed, consider using external fault.
10.60 (ID 300) Start/Stop Logic Selection
Location in the menu:
P2.2.1
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application)
P2.2.1.1
(Multi-Purpose Control Application)
Use this parameter to control the start and stop of the drive with the digital signals.
Table 115: Selections for Parameter ID 300
Selection DIN 1
DIN 2
DIN 3
0
(1)
closed contact = start forward
closed contact = start reverse
-
1
(2)
closed contact = start
open contact = stop
closed contact = reverse
open contact = forward
-
2
closed contact = start
open contact = stop
closed contact = start enabled
open contact = start disabled and drive stopped if
running
can be program-
med for reverse
command
3
(3)(4)
closed contact = start forward (Rising
edge required to start)
(5)
closed contact = start reverse (Rising edge re-
quired to start)
(5)
-
Standard Application and Multi-Step Speed Control Application
4
closed contact = start forward (Rising
edge required to start)
(5)
closed contact = start reverse (Rising edge re-
quired to start)
(5)
-
5
closed contact = start (Rising edge re-
quired to start)
(5)
open contact = stop
closed contact = reverse
open contact = forward
-
6
closed contact = start (Rising edge re-
quired to start)
(5)
open contact = stop
closed contact = start enabled
open contact = start disabled and drive stopped if
running
can be program-
med for reverse
command unless
selected for DIN 2
Local/Remote Control Application and Multi-Purpose Control Application
4
closed contact = start forward
closed contact = reference increases (motor poten-
tiometer reference; this parameter is automatically
set to 4 if parameter ID 117 is set to 4 [Application
4]).
-
5
closed contact = start forward (Rising
edge required to start)
(5)
closed contact = start reverse (Rising edge re-
quired to start)
(5)
-
6
closed contact = start (Rising edge re-
quired to start)
(5)
open contact = stop
closed contact = start reverse (Rising edge re-
quired to start)
(5)
-
7
closed contact = start (Rising edge re-
quired to start)
(5)
closed contact = start enabled
-
AB296635287482en-000301 / DPD00903 | 181