Signal
Description
1=Activate Fieldbus Control
b11 FB DIN 1
-
b12 FB DIN 2
-
b13 FB DIN 3
-
b14 FB DIN 4
-
b15 Reserved
Reserved for internal use
Table 127: Status Word (ProfiDrive)
Signal
Description
b0
Ready To Switch On
0=The drive NOT ready to switch ON
1=The drive is ready to switch ON
b1
Ready To Operate
0=The drive is NOT ready to run
1=The drive is ready to run
b2
Operation Enabled
0=The drive is NOT running
1=The drive is running and ready to release the reference
b3
Fault Active
0=No fault active
1=Fault IS active
b4
Coast Stop Not Active
0=Coast stop active
1=Coast stop NOT active
b5
Quick Stop Not Active
0=Emergency stop active
1=Emergency stop NOT active
b6
Switch On Inhibited
0=No Inhibit
1=The drive is out of fault and coast / quick stop state
b7
Warning
0=NO alarm
1=Alarm IS active
b8
Speed At Reference
0=Speed actual is NOT equal to speed reference
1=Speed actual is equal to speed reference
b9
Fieldbus Control Active
0=Fieldbus Control NOT active
1=Fieldbus Control active
b10
Speed Reference Reached or Exceeded
Indicate if speed actual is below the limit P2.4.16
0=Speed actual is below the speed limit
1=Speed actual is above the speed limit
b11
Not Used
Reserved
b12
Drive Running
0=Drive is stopped
1=Drive is running
AB296635287482en-000301 / DPD00903
322 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide