10.360 (ID 730) Input Phase Supervision
Location in the menu:
P2.7.4
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the supply phase configuration of the drive.
The input phase supervision ensures that the input phases of the AC drive have an approximately equal current.
10.361 (ID 731) Automatic Restart
Location in the menu:
P2.20
(Basic Application)
Use this parameter to enable the Automatic reset function.
The function resets the following faults (maximum three times) (see the User Manual product:
Overcurrent (F1)
Overvoltage (F2)
Undervoltage (F9)
Frequency converter overtemperature (F14)
Motor overtemperature (F16)
Reference fault (F50)
10.362 (ID 732) Response to Thermistor Fault
Location in the menu:
P2.7.21
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the response of the drive to a 'Thermistor' fault.
Setting the parameter to 0 deactivates the protection.
10.363 (ID 733) Response to Fieldbus Fault
Location in the menu:
P2.7.22
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the response of the drive to a 'Fieldbus Timeout' fault.
For more information, see the respective Fieldbus Board Manual.
Selection num-
ber
Selection name
Description
0
No Action
No response
1
Warning
Warning
2
Fault
Fault, stop at fault according to parameter ID 506.
3
Fault, Coast
Fault, stop at fault always by coasting.
4
Warning: PresetF
Warning, frequency reference set to fieldbus fault preset frequency (parameter ID 1801).
(1)
5
Warning: PreFreq Warning, frequency reference set to previous frequency
1
VACON
®
NXP drives, Multi-purpose Control application only.
10.364 (ID 734) Response to Slot Fault
Location in the menu:
P2.7.23
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the response of the drive to a 'Slot Communication' fault.
Set here the response mode for a board slot fault due to missing or broken board.
See parameter
ID 732
.
AB296635287482en-000301 / DPD00903