P2.3.12
(Standard Application)
P2.3.22
(Local/Remote Control Application, Multi-step Speed Control Application, PID Control Application)
P2.3.6.1
(Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to connect the analog output signal 2 to the selected analog output.
The signal selection is done with "Terminal to Function" (TTF) programming. See
10.626 "Terminal to Function" (TTF) Programming
10.210 (ID 472) Analog Output 2 Function
Location in the menu:
P2.3.13
(Standard Application)
P2.3.23
(Local/Remote Control Application, Multi-step Speed Control Application, PID Control Application)
P2.3.6.2
(Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the function for the analog output 2 signal.
10.211 (ID 473) Analog Output 2 Filter Time
Location in the menu:
P2.3.14
(Standard Application)
P2.3.24
(Local/Remote Control Application, Multi-step Speed Control Application, PID Control Application)
P2.3.6.3
(Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to set the filtering time of the analog output 2 signal.
10.212 (ID 474) Analog Output 2 Inversion
Location in the menu:
P2.3.15
(Standard Application)
P2.3.25
(Local/Remote Control Application, Multi-step Speed Control Application, PID Control Application)
P2.3.6.4
(Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to invert the analog output 2 signal.
See
10.69 (ID 309) Analog Output 1 Inversion
.
10.213 (ID 475) Analog Output 2 Minimum
Location in the menu:
P2.3.16
(Standard Application)
P2.3.26
(Local/Remote Control Application, Multi-step Speed Control Application, PID Control Application)
P2.3.6.5
(Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to set the minimum value of the analog output 2 signal.
See
10.70 (ID 310) Analog Output 1 Minimum
10.214 (ID 476) Analog Output 2 Scale
Location in the menu:
P2.3.17
(Standard Application)
P2.3.27
(Local/Remote Control Application, Multi-step Speed Control Application, PID Control Application)
P2.3.6.6
(Multi-purpose Control Application, Pump and Fan Control Application)
Use this parameter to set the scaling factor for the analog 2 output.
See
10.71 (ID 311) Analog Output 1 Scale
.
10.215 (ID 477) Analog Output 2 Offset
Location in the menu:
P2.3.3.7
Use this parameter to add offset to the analog output 2.
Add -100.0% to 100.0% to the analog output signal.
AB296635287482en-000301 / DPD00903
226 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide